Product Name: Formed Wire Suspension Clamp for Conductor

Product Number: 026

Product Details

 

 

Application and Function:

 

Formed wire suspension clamp, intended to fix conductor onto insulator chains on straight-line pole, or hang ground wire onto straight-line pole, may replace such vessel suspension clamps as XGU, XGF that widely used now in line.

 

 

Installation of Formed Wire Suspension Clamp for Conductor

 

 

Picture of Formed Wire Suspension Clamp for Conductor installation steps, product functions and applications.

Components: helical pre-twisted rod, rubber insert, metal clamp, U-strap, open bolt 

 

 

Picture of Formed Wire Suspension Clamp for Conductor installation steps, product functions and applications.

1.   Tighten conductor, determine insulator’s hang-point on conductor, and mark it out. For not damaging conductor, should use soft pen or carbon rod. And then adjust conductor, having enough space and room to install suspension structural reinforcing rod;

 Picture of Formed Wire Suspension Clamp for Conductor installation steps, product functions and applications.

2.   Make the rubber insert center aligned with conductor mark, fix insert with gum tape there;

 Picture of Formed Wire Suspension Clamp for Conductor installation steps, product functions and applications.

 correct installation

3.   Make the structural reinforcing rod center aligned to the rubber insert center, and wind the pre-twisted rod around conductor on both sides of insert (two pitches on both sides). Note: not deform the structural reinforcing rod when winding, ensure no gap between pre-twisted rod and insert; 

 Picture of Preformed Line Products (Formed Wire Suspension Clamp for Conductor) installation steps, product functions and applications.

   incorrect installation

structural reinforcing rod is wound around insert as shown;

 Picture of Preformed Line Products (Formed Wire Suspension Clamp for Conductor) installation steps, product functions and applications.

4.   After all rods are wound on insert, check and determine no crossover here. It may be installed singly, or multi-installed as shown, leave with both ends of structural reinforcing rod, fasten up onto conductor one by one finally; 

 Picture of Preformed Line Products (Formed Wire Suspension Clamp for Conductor) installation steps, product functions and applications.

5.   As shown, wind structural reinforcing rods are around conductor totally. Note: in the whole winding process, using no tool to avoid from damaging cable;   

 Picture of Preformed Line Products (Formed Wire Suspension Clamp for Conductor) installation steps, product functions and applications.

6.   Install both metal clamps in place of center, fasten lug up, regulate both metal clamp lugs and screw-hole on lug, keep them coincided for installing bolt;

 Picture of Preformed Line Products (Formed Wire Suspension Clamp for Conductor) installation steps, product functions and applications.

7.   Installing bolt is through matching hardware, fasten nut until gripping liner is leveled, set up pin. Note: not screw too much, not close both of the metal lugs to the metal clamp too much;

 Picture of Preformed Line Products (Formed Wire Suspension Clamp for Conductor) installation steps, product functions and applications.

8.   Installation is over.

 

 

 

Instruction:

 1.   It is a fine-designed product, for ensuring quality, it should be packed well in carton, be more careful in transportation and installation, to avoid from damage or deformation;  

 2.   It is a special one-off product, in no condition, it may be reused and changed;  

 3.   The maximum installation angle: if the turn angle between the supporting point and line is less than 30o, should select the single supporting-point suspension clamp. If 30o–60o, the double-supporting-point suspension clamp shall be preferred;  

 4.   The pre-twisted rod is matched in factory, not be mixed. Its direction in each set shall not be mixed or reversed;

 5.   For a line of 230KV or less, the axial misplace of pre-twisted rod shall be maintained within 20mm; for 345KV or more, the misplacement shall not surpass 10mm;

 6.   If in doubt, please contact us.  